8MWh VRB - ESSTM |
|
|
Load
Output Power Rating |
1.2MVA
(2 x 600kVa Modules) |
|
Energy
Storage duration |
8
hours |
|
Input
Voltage (rms): |
|
|
-
Nominal Supply Voltage Vnominal |
480
V (L-L) |
|
-
Maximum Supply Voltage Vnominal |
110%
of Vnominal |
|
Nominal
Frequency |
60Hz |
|
Output
Voltage: |
480V
3 phase 60Hz |
|
Voltage
Regulation |
<
±1% Continuously |
|
Reactive
Energy Compensation |
±
1000kVar |
|
DC
Bus Voltage |
200
- 350V |
|
Transient
Performance - Load |
Meets
ITIC Performance Spec. for Transient Responses: Vdip< 15% for 2 Cycles |
|
Load
Terminal Overvoltage |
125%
of Vnominal |
|
Short
Circuit Capability |
300%
of Full Load |
|
Minimum
Efficiency (Power Out/Power In) PCS |
>96%
@ Full Load |
|
Maximum
Overload Capacity < 10 minutes |
120% |
|
Maximum
Overload Capacity < 3 seconds |
130% |
|
Reliability |
>99.99%
(4 Nines) Minimum SPoF |
|
Harmonic
Performance |
Meets
IEEE 519 |
|
Voltage
Unbalance at Input Terminals |
<
2% |
|
Communications
Protocols |
Modbus,
DNP 3.0, TCP/IP |
|
Communication
Connection Interfaces |
RS232,
RS 485, and Ethernet |
|
Environmental |
0
to +40°C (Controlled Building) |
|
Mass
kg - Storage Tanks (With Electrolyte) |
600,000kg |
|
-
Stacks |
28,000kg
(22 Modules) |
|
-
Power Converter and Controls |
1850kg |
|
Dimensions
8MWH |
4
x 12 x 20m (240m2) Can be Split Over Multiple Levels |
|
Noise
Levels dB (A Weighted) |
<70dB(A)
at 3 Meters |
|
Life
of System Before Replacement of Membranes |
>10
years |
|
Annual
Operations & Maintenance Costs |
$0.008/kWh |
VRB-ESS is capable of providing a short-term power output of approximately 5 times nominal for periods of 1 minute in every hour. The response time for this is virtually instantaneous of the order of 5 milliseconds. The PCS has to be rated accordingly. This feature allows the VRB-ESS to support motor starts, which have large inrush currents, and to provide voltage dip ride through as well as alleviating voltage flicker caused by rolling mills and arc-furnaces.